CBY Airport Water Extension

Submittal 234

Field quality-control reports (domestic water pressure tests)
CBY Airport Water Extension
Project I0297.24002
Airport Road, Yakutat, Alaska 99689
Owner: City and Borough of Yakutat
Engineer: RESPEC
Specification section
22 11 16
Type
Test report
Status
Not yet submitted

Description

Specification 22 11 16 Domestic Water Piping, paragraph 1.04 B. Informational submittal; 3.11 requires a 100 psig (80 psi max for PEX) four-hour static test, a separate report for each segment tested complete with a diagram of the portion tested, and reports of corrective action. During construction.

Disposition

☐ Approved☐ Approved as noted☐ Revise and resubmit☐ Rejected☐ For record only

History

Printed Oct 12, 2026, 8:56 AM by VisitorWorkhorse · Hesiod Holdings