Submittal 676
Hydrostatic pressure test reports
CBY Airport Water Extension
Project I0297.24002
Airport Road, Yakutat, Alaska 99689
Owner: City and Borough of Yakutat
Engineer: RESPEC
- Specification section
- 33 11 00
- Type
- Test report
- Status
- Not yet submitted
Description
Specification 33 11 00 Water Distribution Piping, paragraph 1.06 A.1. Test at not less than 150 psig for two hours per AWWA C600 (ductile iron) and AWWA C906 (HDPE), before joints are covered; prepare reports and submit to Engineer of Record (3.11 B, C). During construction.
Disposition
☐ Approved☐ Approved as noted☐ Revise and resubmit☐ Rejected☐ For record only