Submittal 483
Wiring device field test and inspection reports
CBY Airport Water Extension
Project I0297.24002
Airport Road, Yakutat, Alaska 99689
Owner: City and Borough of Yakutat
Engineer: RESPEC
- Specification section
- 26 27 26
- Type
- Test report
- Status
- Not yet submitted
Description
Specification 26 27 26 Wiring Devices, paragraph 1.03 B. Field quality-control reports (listed under Action Submittals); per 3.03 C and 3.04 C assemble and submit test and inspection reports for switches and for receptacles (polarity, line voltage, voltage drop, ground continuity not greater than 2 ohms, GFCI trip). During construction.
Disposition
☐ Approved☐ Approved as noted☐ Revise and resubmit☐ Rejected☐ For record only