291 Inertia base and vibration isolator shop drawings

Details

Specification section
23 05 48
Type
Shop drawing
Priority
Normal
Description
Specification 23 05 48 Mechanical Sound, Vibration, and Seismic Control, paragraph 1.05 B.1. Indicate inertia bases and locate vibration isolators with static and dynamic load on each; show base dimensions, equipment center of gravity, individual isolators per support point, mounting bracket details, equipment mounting bolt locations, and concrete support sizes; all submittals stamped and signed by the manufacturer's registered PE (1.05 I).