708 Sanitary sewer hydrostatic leakage test results
Details
- Specification section
- 33 31 13
- Type
- Test report
- Priority
- Low
- Description
- Specification 33 31 13 Sanitary Utility Sewerage Piping, paragraph 3.06 A. Hydrostatic test with 6 feet of head above the upper end held 4 hours for absorption then 1 hour for leakage, allowable E = 0.002 x D x L gallons per hour; repeat after repairs until within allowance. During construction. Read from the section with medium confidence; confirm the requirement before sending.