CBY Airport Water Extension

Submittal 545

Generator infrared scan certified report
CBY Airport Water Extension
Project I0297.24002
Airport Road, Yakutat, Alaska 99689
Owner: City and Borough of Yakutat
Engineer: RESPEC
Specification section
26 32 13.13
Type
Test report
Status
Not yet submitted

Description

Specification 26 32 13.13 Diesel-Engine-Driven Generator Sets, paragraph 3.05 K.2. After Substantial Completion but not more than 60 days after final acceptance perform infrared scan of each power termination and bus connection at maximum load; certified report identifies terminations checked, scanning results, deficiencies, remedial action, and post-remedy observations; provide device calibration record. Closeout.

Disposition

☐ Approved☐ Approved as noted☐ Revise and resubmit☐ Rejected☐ For record only

History