413 Grounding system field test and inspection reports

Details

Specification section
26 05 26
Type
Test report
Priority
Normal
Description
Specification 26 05 26 Grounding and Bonding for Electrical Systems, paragraph 1.03 B. Field quality-control reports (listed under Action Submittals); per 3.05 E collect, assemble, and submit test and inspection reports, reporting measured ground resistances exceeding 10 ohms for systems 500 kVA and less; tests are witnessed by Engineer and performed by fall-of-potential method per IEEE 81. During construction.